is removed, the installation can be continued.
2. Fluctuation scope of power line voltage is usually between +10%, if the voltage is not in
this scope, please take measures to regulate it.
3. A leak-protector and a master switch should be provided on the line. The fuse is
forbidden to be replaced by the copper wire and other wires. Please select the appropriate
fuse according to the maximum of the electric power consumption, which comprises 1.5 to
3 times of the maximum current of the Atlantis Solar Air conditioner and the current of
other electric appliances.
4. The power cord should be provided with effective ground wire. If not, the installer
should refuse to install and clearly explain.
5. The power source must be supplied only for the Atlantis Solar Air conditioner and
should satisfy following items.
Form 5. Comparison of the Standards of Electric Conductor Cross Section Area (Diameter
of Wire), Power Switch, Fuse and Load Current
Special power distribution equipment and
electric wire for the air conditioner
Power distribution equipment and electric wire
for the power bus
Air
conditioner’s
maximum
current (A)
Electric
conductor’s
cross-sectio
nal area(m
2
)
Standard spec
(A) of the
socket or
power of the
switch /fuse.
Circuit’s
maximum
current×(1.
5 to 3
times) (A)
Electric
conductor’s
cross
sectional
area(m
2
)
Standard spec
(A) of the
power switch /
the fuse
10 1 or 1.5 16/16 16 1.54 32/25
16 1.5 or 2.5 32/25 25 2.54 63/50
25 2.5 or 4 63/50 32 410 63/50
32 4 or 6 63/50 40 616 100/80
63 1025 125/125